Hydraulic Pressure Sensor and Calibration | Hidromas

Why Sensor Accuracy and Calibration are Important in Hydraulic Pressure Measurement

Why Sensor Accuracy and Calibration are Important in Hydraulic Pressure Measurement — Hidromas

Calibrating a hydraulic pressure sensor establishes the relationship between the value displayed by the device and the reference. It is not the same process as adjusting the sensor itself. It cannot be assumed that a calibrated device will provide flawless measurements at every pressure, temperature, and indefinitely. For accurate testing decisions, the range, accuracy definition, and measurement uncertainty must be considered together.

In tipper hydraulics, measurement results can form the basis for evaluating a valve setting, pump behavior, or system limit. Errors in measurement can lead to replacing a working part or overlooking out-of-limit behavior. Therefore, sensor selection should not be based solely on connection thread and maximum pressure.

Technical checklist

Feature The question to be asked Influence of the decision
Measurement range Where is the work area? At low values, the relative error may increase.
Definition of truth Full range reading or not? Percentages cannot be directly compared.
Calibration scope What points and conditions exist? The usage area may not be covered.
Dynamic response Will the sudden event be measured? Static accuracy may not be sufficient.

Read the essence of the statement of truth.

The percentage error given in the catalog may be defined according to the exact measurement range or the value read. These two definitions do not yield the same result at low pressures. Temperature effects, repeatability, and long-term variation may also be outside the scope of a single number in the catalog.

Let's say a hypothetical sensor has a range of 0–400 bar and a stated error of 0.5% of the full range. This expression corresponds to an error limit of 2 bar under the conditions where the definition is valid. In a 20 bar measurement, the same 2 bar is 10% of the reading. This example is not a product feature or acceptance criterion.

Match the calibration document with the test.

The document should include device identification, references used, results, and uncertainty information. NIST's measurement uncertainty approach highlights the importance of assessing uncertainty along with the result. Matching the serial number on the certificate with the sensor in the field is a fundamental but frequently overlooked check.

The calibration interval is determined by the frequency of use, exposure conditions, and past stability. Dropping, excessive pressure, or unexpected zero drift may require rechecking before the calendar expires. The statement "Calibrated last year" alone does not indicate current suitability.

Also check the chain outside the sensor.

The logger's scale setting, power supply, cabling, and unit conversion in the software all affect the result. If the sensor is working correctly but the software uses an incorrect range, the entire record can be inaccurate. The pressure type must also be clearly indicated: gauge pressure, absolute pressure, and differential pressure are not interchangeable.

The location of the measurement port and the connection volume become particularly important in transient events. The installation process is carried out by checking the system power; the installation and maintenance aspects of hydraulic safety are covered by ISO 4413. If the result is very close to the limit, a definitive conformity decision cannot be made without taking the uncertainty into account.

Match the calibration result with the usage range.

A sensor's documentation may contain results for different pressure points. It's important to check if the area where the actual test was conducted falls within this range. Focusing solely on high-pressure performance is inappropriate, as most measurements occur at low pressure. The total error description in the catalog and the calibration report should be read together. This allows you to assess the sensor's suitability for its intended purpose, without considering only its maximum range.

The calibration conditions may differ from the temperature and mounting conditions in the field. How these differences might affect the results should be considered in the measurement plan. A certificate does not mean that the device will perform the same in every environment. The operating conditions of the sensor should be checked, especially in vehicle applications where temperature variations are significant. The limitations of the measurement system also define the limitations of the technical interpretation in the report.

Interpret the zero control based on the type of pressure.

A device that measures gauge pressure and a device that measures absolute pressure do not use the same reference. Therefore, it should not be assumed that the display must necessarily show zero in a situation that appears to be pressureless. First, it is necessary to understand what the sensor is measuring. The conclusion that the device is experiencing zero drift cannot be drawn without correcting scale and unit errors. The control to be applied should be based on the manufacturer's instructions and a reliable measurement setup.

Adjusting the settings at the zero point does not automatically correct the accuracy at other pressure points. Simply setting the display to the desired value at a single point does not replace calibration. If an adjustment has been made, the previous and subsequent settings should be recorded. Deleting the adjustment history, especially while a fault investigation is ongoing, makes it difficult to re-evaluate past measurements. The date and setting from which the device was used should be clearly displayed.

Check the conversion of an electrical signal into pressure.

Even if the sensor is producing a correct signal, the wrong range may have been selected in the data logger. The signal type, lower and upper end values, supply conditions, and software unit should all be verified together. A problem with the cable connection can also appear as a pressure change on the record. Knowing that the measurement chain is not solely composed of the sensor helps prevent unnecessary component replacements.

For example, even if the exact range of a sensor is changed, the old scale in the recording software may be preserved. The graph may appear correct, but all the numbers may be incorrect. Such situations may not be easily detected by visual graph analysis alone. It is useful to perform validation with known reference conditions in the setup. The validation method and acceptable limit should be determined by the authorized team in a manner consistent with the purpose of the measurement.

Address uncertainty using the decision rule.

If the measured value is very close to the technical limit, making a definitive decision based solely on the rounded number can be misleading. The measurement uncertainty and the decision-making method used should be evaluated. This does not mean automatically rejecting all products at the limit. The aim is to clearly demonstrate how confidently the result can be interpreted. If a decision rule is included in the technical specification, the report should be linked to it.

If two sensors show different readings, both the magnitude of the difference and the measurement conditions are examined. Whether measurements were taken at the same point and at the same time, the type of pressure used, and any uncertainties in the devices are checked. It is not assumed that a new device is always accurate and an old one is always inaccurate. The comparison should be based on traceable measurement data, not the age of the device.

Include sensor history in maintenance decisions.

When determining the calibration interval, the frequency of use and the conditions to which the device is exposed can be considered. Devices exhibiting excessive pressure, impact, or unexpected behavior may require inspection before the planned date. Regularly monitoring the device's past results provides better information about its stability. The schedule alone does not account for all technical risks; usage records and inspection findings should be evaluated together.

In pressure assessments conducted with Hidromas, it is important to share the sensor's identity, report, and data logging device settings. This allows for a more accurate investigation of whether the measurement discrepancy originates from the product or the measurement chain. A reliable measurement system supports both the initial diagnosis and the final verification of maintenance. The comparability of results depends on the consistency of the method as well as the equipment used.

The calibration certificate must be checked to ensure the product ID matches the sensor in the field. Traceability is incomplete for sensors with unreadable labels or those used with documentation from another device. The certificate date alone does not indicate suitability for use; the measurement range and results must also be examined. Establishing the necessary decision rule makes it clearer how to handle borderline values. The number of digits displayed should not be used as an indicator of accuracy, replacing this technical assessment.

Frequently Asked Questions

Does the calibration device correct it automatically?

No. Calibration determines the measurement relationship. If an adjustment has been made, this must be stated separately and the results re-verified.

Is a wider-range sensor always better?

No. Even if it offers a strength advantage, it may not meet the resolution and error requirements in the working area. The selection is made for measurement purposes.

If the two sensors read different readings, which one can be trusted?

First, the point, pressure type, scale, and calibration status are compared. It is not appropriate to accept a sensor as correct simply because it is new.

Include the sensor ID, calibration information, and measurement scheme in the test report to be shared with Hidromas. These records allow for meaningful comparison of tests performed at different times.